NAJS automatic flash speed multi-position transformer calibration device, is the South Australian ElectricCompanytoadapt to themoderntransformer calibration fast and accurate characteristics of the development of a new generation of transformer calibration device. The device consists ofNAJSautomaticflashspeedmulti-position transformer calibration device, the current load box, control cabinet, current transformer test stand and other components. In the premise ofmaintainingtheoriginaltechnicalcharacteristics of the current transformer in the rapid measurement of the rapid positioning of test points, and the load box, a variety of variable ratio of thetransformercover,etc.have beengreatly improved.
Product Features
(1) The fine adjustment of the device uses a programmable source technology, the test point of the positioning morequicklyandaccurately.
(2) the device in a number of current transformer measurement speed has been a qualitative improvement in the 3-5 minutes of timecanbemeasured inanyof the twe*e transformers than any current transformer.
(3) The device is equipped with 5A standard current transformer, the current load box configuration 5A load value of2.5VA-60VA,thevoltage loadboxconfiguration 100V load value from 1.25VA-158.75VA basically meet the requirements of users. The load box can be switched automatically during measurement.
(4) The device can be used for the regulation of the transformer and non-regulation of the measurement, the user canspecifythemeasurement ofanypercentage of the measurement.
Technical indicators
(1) environmental conditions
Temperature: 5 °C to 40°C
Relative humidity:
Altitude:
Power frequency: 50Hz ±0.5Hz
Power supply voltage: 220V ±5V
(2) Measuring range:
F: 0.0000% to 200.0% δ: 0.000 'to 999.9'
R: 0.0000? To 60.0? X: 0.0000? To 60.0? G: 0.0000 mS to 60.0 mS
Measurement objects: CT, PT, impedance, admittance.
(3) the basic error:
In-phase component: ΔX =±(X×2%+Y×2%±2 words)
Quadrature component: ΔY=±(Y×2%+±X×2%×34.38)±5 words
"X", "Y" - the displayed value of the instrument
"5 words" - quantization error of the instrument
Dial indicator: Level 1
(4) Scope of work:
Current: (1% -149%) In (In = 5A)
(5% -149%) In (In = 1A)
Workload: Current: To for Tx
(5) Dimensions (mm)
Horizontal table body: 1500 (L) ×780 (W)×1030 (H)
Vertical platform body: 670 (L) ×630 (W)×1570 (H)